Appendix C: Applications
226 P/N 3102352-EN • REV 005 • ISS 28DEC18
Notes
Set the alarm activation count for this correlation to 1.
For this correlation only, enable in-suite signal silence.
In-Suite Signal Silence Correlation
Input
Output
Occupant and hallway inputs on all
floors Occupant sounders on all floors
How this application works
This application silences the audible alarm signals inside dwelling units, except on the floor of
the alarm.
For example, if an alarm occurs on the third floor:
The Floor 3 Correlation turns on the sounders on the floor of the alarm (including those
inside dwelling units).
The Hallway Correlation turns on hallway sounders throughout the building.
The In-Suite Signal Silence Correlation turns on sounders in residences on all other floors.
After 60 seconds, the In-Suite Signal Silence Correlation, which has in-suite signal silence
enabled, silences sounders inside dwelling units on all other floors. These signals remain
off until the in-suite signal silence timer expires or a subsequent alarm comes in.