Firmware 02.00 - DMS 2.1 EN - 03/2011 L 277
8400 motec | Software Manual
Parameter reference
Parameter list | C00601
C00601
C00604
C00606
C00607
Parameter | Name:
C00601 | Del. resp.to fault: DC bus overvoltage
Data type: UNSIGNED_16
Index: 23974
d
= 5DA6
h
Delay times for error responses
Setting range (min. value | unit | max. value)
0.00 s 65.00
Subcodes Lenze setting Info
C00601/1 2.00 s Delay time for error activation "DC-bus overvoltage"
In case of DC-bus overvoltage, an error is only
transmitted after this delay time has elapsed.
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00604 | Resp. to device overload (Ixt)
Data type: UNSIGNED_8
Index: 23971
d
= 5DA3
h
Response if the adjustable device utilisation threshold (C00123) is reached.
The current device utilisation is displayed in C00064
.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
4 WarningLocked
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00606 | Resp. to motor overload (I²xt)
Data type: UNSIGNED_8
Index: 23969
d
= 5DA1
h
Response if the adjustable motor overload threshold (C00120) is reached.
The current thermal motor load is displayed in C00066
.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
4 WarningLocked
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00607 | Resp. to max. speed reached
Data type: UNSIGNED_8
Index: 23968
d
= 5DA0
h
From version 02.00.00
Response when the maximum input frequency of the actual speed value feedback via the digital inputs has been
reached.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
4 WarningLocked
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1

Table of Contents

Other manuals for Lenze 8400 motec

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 motec and is the answer not in the manual?

Lenze 8400 motec Specifications

General IconGeneral
Input Voltage3-phase 380V to 480V AC
Control ModeVector control
CommunicationCANopen, PROFIBUS, Ethernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, short-circuit, overtemperature
Relative Humidity≤ 95 %, no condensation
AltitudeUp to 1000m above sea level
Storage Temperature-20°C to 65°C