8400 motec | Software Manual
Device control (DCTRL)
Device commands (C00002/x)
36 L Firmware ≤ 02.00 - DMS 2.1 EN - 03/2011
4.1.2 Load parameter set 1
The C00002/2
= "1: On / start" device command reloads all parameters from the memory
module to the controller.
The DIP switches are not used anymore to overwrite data.
Can only be executed if the controller is inhibited; otherwise, the feedback C00002/
2 = "6: No access - controller inhibit" will be returned.
All parameter changes which have been carried out after the last time the parameter
set was saved will be lost!
This controller command has an effect on the settings of the parameters of the
operating system, application and module.
How to load the parameter set 1 from the memory module:
1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/
Inhibit controller" device command (C00002/16
= "0: Off / ready").
2. Execute the "Load parameter set 1" device command:
C00002/2
="1:On/start"
The load process may take a couple of seconds. After the device command has been
called in C00002/2
, a dynamic status information ("Work in progress" "Off /
Ready") is returned.
Note!
• When the device is switched on, all parameters are automatically loaded
from the memory module to the main memory of the controller.
– When the DIP switches are active (DIP switches S1\1 = "ON"), the controller
operates with the settings made via the DIP switches and displays them in
the corresponding codes.
• The controller has a parameter set.
– Up to 16 freely selectable parameters can be switched over via the basic
Parameter change-over
function. ( 172)