EasyManuals Logo
Home>LG>Air Conditioner>Multi V CRUN Series

LG Multi V CRUN Series User Manual

LG Multi V CRUN Series
249 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
114 Indoor Unit
Operation Details
3. Operation Details
(1) MAIN UNIT FUNCTION
DISPLAY
Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Sleep Timer Indicator
ON while in sleep timer mode, OFF when sleep timer cancel or appliance operation pause.
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
OFF except when hot start during heating mode operation or while in defrost control.
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temperature, the compressor and the out-
door fan stop.
When it reaches 0.5°C above the setting temperature, they start to operate again.
Compressor ON Temperature Setting Temperature +0.5°C
Compressor OFF Temperature Setting Temperature -0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temperature is automatically set according to the intake air temperature.
26°C Intake Air Temperature 25°C
24°C Intake Intake Air Temperature <26°C Intake Air Temperature -1°C
18°C Intake Intake Air Temperature <24°C Intake Air Temperature -0.5°C
Intake Air Temperature <18°C 18°C
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temperature is between compressor on temperature and compressor off temperature,
10-min dehumidification operation and 4-min compressor off repeat.
Compressor ON temperature Setting Temperature +0.5°C
Compressor OFF temperature Setting Temperature -0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

Table of Contents

Other manuals for LG Multi V CRUN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V CRUN Series and is the answer not in the manual?

LG Multi V CRUN Series Specifications

General IconGeneral
BrandLG
ModelMulti V CRUN Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals