24 Indoor Unit
Operation detail
3. Operation detail
Time Delay Safety Control
5 sec
...
Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.
5 sec
...
The 4-way valve is ceased for 5 sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode when compress is off.
While compressor is running, it takes 3~5 seconds to switch.
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Intake Air Temperature
COMP. ON
(SET TEMPERATURE +0.5°C)
COMP. OFF
(SET TEMPERATURE -0.5°C)
More than More than
3 minutes 3 minutes
Selecting Selecting Selecting
fan speed fan speed fan speed
INDOOR FAN Low Low
(1) The function of main control