Service Manual 49
Specifications
1. Specifications
Notes:-
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notification.
4. L.E.V. : Linear Expansion Valve
Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m
3
/min x 35.3
Model Unit
W
Cooling Capacity kcal/h
Btu/h
W
Heating Capacity kcal/h
Btu/h
Casing
Dimensions (W*H*D) mm
inch
Coil
Rows*Steps*Fin Pitch
inch
Moisture removal l/h
Fan Model
Type
Motor Output
W
Air Flow Rate(H/M/L) CMM
CFM
External Static Pressure
Pa
Drive
Speed control
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Pipe Connections
Liquid Side mm(inch)
Gas Side mm(inch)
Drain Pipe(Internal Dia.)
mm
Net Weight kg(lbs)
Noise Level(SoundPress,1.5m,H/M/L) dBA±3
Power Supply Ø,V,Hz
Power Cable
AWG#:P*mm
2
Refrigerant Control
Standard Accessories
CRNN076BNG0 CRNN096BJG0 CRNN126BJG0
2,100 2,600 3,500
1,806 2,235 3,009
7,165 8,871 11,942
2,363 2,925 3,923
2,031 2,515 3,385
8,061 9,980 13,435
Galvanized Steel Plate
783*220*520 873*220*520 873*220*520
30.8*8.7*20.5 34.3*8.7*20.5 34.3*8.7*20.5
2*9*14 2*9*14 2*9*14
1.0 1.0 1.5
D-7K D-9K D-12K
Sirocco Fan Sirocco Fan Sirocco Fan
13 17 20
6.4/5.9/5.4 7.0/6.5/6.0 10.2/9.2/8.2
226/208/191 247/230/212 360/325/290
00 0
Direct
Steps Control
Microprocessor,Thermistat for cooling and heating
Foamed polystyrene
Fuse,Thermal Fuse for Fan Motor
6.35(1/4) 6.35(1/4) 6.35(1/4)
12.7(1/2) 12.7(1/2) 12.7(1/2)
25 25 25
23(50.7) 24(52.9) 24(52.9)
36/34/32 37/35/33 38/36/34
1,220~240,50 1,220~240,50 1,220~240,50
12:3 * 2.5 12:3 * 2.5 12:3 * 2.5
LEV LEV LEV
Owner's Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws

Table of Contents

Other manuals for LG Multi V CRUN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V CRUN Series and is the answer not in the manual?

LG Multi V CRUN Series Specifications

General IconGeneral
BrandLG
ModelMulti V CRUN Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals