EasyManuals Logo
Home>LG>Air Conditioner>Multi V CRUN Series

LG Multi V CRUN Series User Manual

LG Multi V CRUN Series
249 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #135 background imageLoading...
Page #135 background image
Service Manual 135
Operation Details
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to oper-
ate procedures automatically to the previous operating conditions.
Remote Control Operation Mode
When the remote control is selected by the slide switch on the main unit, the appliance operates according
to the input by the remote control.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in
cooling cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the
indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that
the remote control signal cannot be received.

Table of Contents

Other manuals for LG Multi V CRUN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V CRUN Series and is the answer not in the manual?

LG Multi V CRUN Series Specifications

General IconGeneral
BrandLG
ModelMulti V CRUN Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals