208 Outdoor Unit
Installation
2) Adjusting air volume to the height of ceiling
You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to supply the com-
fortable atmosphere to consumers.
Procedure
1. Choose the selectable position in the table after measuring the height of ceiling.
2. In the case of changing the height as "high" or "low", open the rear cover of the wired remote-controller.
3. Move the slide switch to the set position.
4. Close the rear cover and check if it works nomally.
Ceiling height Mode of slide switch Change of air volume Remark
more than 4.0m High Ceiling Increasing
3.2~4.0m Standard -
less than 3.2m Low Ceiling Decreasing
Maunfactured in stan-
dard mode