EasyManua.ls Logo

LG Multi V CRUN Series

LG Multi V CRUN Series
249 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Self-diagnosis function
Service Manual 241
Fault diagnosis and Trouble shooting guide
Title
Display
code
Cause of errorMeaning
No
Execute group
setting
Execute group
setting
Yes
Is the state of
transmission in
outdoor unit normal?
Yes
Check and replace
indoor unit PCB
Repair the
connection
No
Check and replace outdoor
unit PCB
Is the PCB of central
controller normal?
No
Transmission
error from main
PCB in the
outdoor unit
to central
controller
56
Group setting is not carried out
Transmission connector unplugged
Transmission cable misconnected / disconnection
Malfunction of central controller circuit
Malfunction of transmission circuit of indoor unit
Distance between transmission cable and power
cable is not enough
In the case that central
controller can not receive
any signal
from main PCB
successively for 3minutes
Trouble shooting Flow