62 Indoor Unit
Indoor Unit
Convertible
Operation Details
■ Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote
controller and the operation diagram is as following
■ Cooling or Heating Mode with Sleep Mode Auto Operation
• When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Operation( ), the
operation diagram is as following.
Cooling Mode with the Sleep Mode
• The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Heating Mode with the Sleep Mode.
The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air Temperature
COMP. ON
(SET TEMPERATURE +0.5°C)
COMP. OFF
(SET TEMPERATURE -0.5°C)
More than More than
3 minutes 3 minutes
INDOOR FAN Low Low Low Low Low
COMPRESSOR ON OFF ON OFF ON
30 minutes 30 minutes
1°C
1°C
Setting Temperature +3°C
(Compressor OFF)
Setting Temperature
(Compressor ON)
Indoor Fan Med. Med. Med. Med. Med. Med.
Compressor ON OFF ON OFF ON OFF
Intake Air Temperature
COMP. ON
(SET TEMPERATURE +0.5°C)
COMP. OFF
(SET TEMPERATURE -0.5°C)
More than More than
3 minutes 3 minutes
Selecting Selecting Selecting
fan speed fan speed fan speed
COMPRESSOR ON OFF ON OFF ON
INDOOR FAN Low Low