98 Indoor Unit
Operation Details
Fuzzy Operation
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed
since the operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and
only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake
air temp at that moment as follows.
24°C Inatake Air Temp Fuzzy Operation for Cooling
21°C Inatake Air Temp<24°C Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for
10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more
below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the
compressor is turned on.
Compressor ON Temp Setting Temp +0.5°C
Compressor OFF Temp Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
26°C Intake Air Temp 25°C
24°C Intake Air Temp<26°C Intake Air Temp + 1°C
22°C Intake Air Temp<24°C Intake Air Temp + 0.5°C
18°C Intake Air Temp<22°C Intake Air Temp
Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem-
perature.
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more
below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the
compressor is turned on.
Compressor ON Temp Setting Temp + 0.5°C
Compressor OFF Temp Setting Temp+0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
26°C Intake Air Temp 25°C
24°C Intake Air Temp<26°C Intake Air Temp+1°C
22°C Intake Air Temp<24°C Intake Air Temp+0.5°C
18°C Intake Air Temp<22°C Intake Air Temp
Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.

Table of Contents

Other manuals for LG Multi V CRUN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V CRUN Series and is the answer not in the manual?

LG Multi V CRUN Series Specifications

General IconGeneral
BrandLG
ModelMulti V CRUN Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals