INSTALLER SETTING
ENGLISH
182
INSTALLER SETTING
Outdoor temp. for heating stages (air conditioner)
It is a function that sets outdoor temperature values for two stage heating.
if user set outdoor temperature T1 and T2, Indoor unit will select heating stage between Indoor
unit operation and heater operation.
OK
SW Version Setting value Option T1 value T2 value
~2.08.2a
Not Use - - -
Use -
-23 ~ 16 °C -23 ~ 51 °C
(-10 ~ 60 °F) (-10 ~ 130 °F)
2.09.0a~
Not Use - - -
Auto -
-23 ~ 16 °C -23 ~ 51 °C
(-10 ~ 60 °F) (-10 ~ 130 °F)
Manual
Heat pump
- -Heater
Heater + H/P
※ Even if the remote control version is 2.09.0a or more, Features may not be supported.
Setting value Description
Use Display energy consumption data which outdoor unit estimated
Not Use Not display energy consumption data which outdoor unit estimated
Estimated energy display (air conditioner)
This function can set to display energy data which outdoor unit estimated power consumption
data without wattmeter.