Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
IEC: SigGGIO1 selection
104 064
060 000: MAIN: Without function
[spacer]
Optional signal assignment for a transmission per communication protocol
IEC 61850 based on the selection table of the binary inputs (opto coupler
inputs).
[spacer]
IEC: Diff. local time
104 206
0 -1440 1440 min
[spacer]
Time difference between UTC and local time at the devices' substation (IED).
[spacer]
IEC: Diff. dayl.sav. time
104 207
60 -1440 1440 min
[spacer]
Time difference of the daylight saving time to standard time.
[spacer]
IEC: Switch.dayl.sav.time
104 219
1: Yes
[spacer]
This setting defines whether an automatic switching to daylight saving time is
wanted.
[spacer]
IEC: Dayl.sav.time start
104 220
5: Last
[spacer]
IEC: Dayl.sav.time st. d
104 221
7: Sunday
[spacer]
IEC: Dayl.sav.time st. m
104 222
3: March
[spacer]
These three parameters define the date (e.g. at what day of the year) for
switching from standard time over to daylight saving time. Available for
IEC: Dayl.sav.time start are the values First, Second, Third, Fourth, and
Last. For IEC: Dayl.sav.time st. d the seven weekdays are available so
that for example a setting like “on the last Sunday in March” may be used.
[spacer]
IEC: Dayl.sav.t.st.0:00 +
104 223
120 0 1440 min
[spacer]
Time period in minutes after midnight when daylight saving time is switched to
standard time. If for example the clock is advanced one hour from 2:00 AM to
3:00 AM the parameter IEC: Dayl.sav.t.st.0:00 + is set to 120 (minutes).
[spacer]
IEC: Dayl.sav.time end
104 225
5: Last
[spacer]
IEC: Dayl.sav.time end d
104 226
7: Sunday
[spacer]
IEC: Dayl.sav.time end m
104 227
10: October
P631
7 Settings
7-32 P631/EN M/R-11-C // P631-310-650