Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
IEC: IED name
104 057
2:
[spacer]
Explicitly assigned unit name for the function in the system (IED); is part of the
Logical Device Name.
Setting is carried out with the IED Configurator.
Important note: According to the IEC standard the name must consist of only
letters (A..Z, a..z), digits (0..9) and underscore characters (_), and neither a digit
nor the underscore character must be the first character. Note that a non-
standard name causes problems with the IEC 61850 communication.
[spacer]
IEC: IP address
104 001
2:
[spacer]
Assigned IP address of the device for the server function in the system.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: IP Address.
[spacer]
IEC: Subnet mask
104 005
2:
[spacer]
The subnet mask defines which part of the IP address is addressed by the sub-
network and which part by the device that is logged-on to the network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: SubNet Mask.
[spacer]
IEC: Gateway address
104 011
2:
[spacer]
This parameter shows the IPv4 address of the network gateway for
communication links to clients outside of the local network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: Gateway Address.
[spacer]
IEC: SNTP server 1 IP
104 202
2:
[spacer]
IP address of the preferred server used for clock synchronization.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator".
[spacer]
IEC: SNTP server 2 IP
104 210
2:
[spacer]
IP address of the backup server used for clock synchronization.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator".
7 Settings
P631
P631/EN M/R-11-C // P631-310-650 7-31