Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
LIM_1: I<<
015 119
Blocked 0.00 4.00 Inom Fig. 3-139, (p. 3-171)
[spacer]
LIM_2: I<<
016 119
Blocked 0.00 4.00 Inom
[spacer]
Setting for the operate value of I<<.
[spacer]
LIM_1: tI<
015 122
5 0 100 s Fig. 3-139, (p. 3-171)
[spacer]
LIM_2: tI<
016 122
5 0 100 s
[spacer]
Setting for the operate delay of I<.
[spacer]
LIM_1: tI<<
015 123
Blocked 0 100 s Fig. 3-139, (p. 3-171)
[spacer]
LIM_2: tI<<
016 123
Blocked 0 100 s
[spacer]
Setting for the operate delay of I<<.
7 Settings
P631
P631/EN M/R-11-C // P631-310-650 7-89