7.1.3.3 Parameter Subsets
Parameter Address
Default Min Max Unit Logic Diagram
Main function
MAIN: Vnom prim. end a PSx
019 017 019 057 019 061 019 065
110.0 0.1 1500.0 kV
[spacer]
Setting for the primary nominal voltage at end a of the transformer.
[spacer]
MAIN: Vnom prim. end b PSx
019 018 019 058 019 062 019 066
110.0 0.1 1500.0 kV
[spacer]
Setting for the primary nominal voltage at end b of the transformer.
[spacer]
MAIN: Phase reversal a PSx
010 200 010 201 010 202 010 203
0: No swap
[spacer]
MAIN: Phase reversal b PSx
010 204 010 205 010 206 010 207
0: No swap
[spacer]
Setting for the phase reversal function (see description for function group MAIN)
for electrical machines in pumped storage power stations.
Phases to be reversed (A-B swapped, A-B swapped or A-B swapped) may be set
separately for each end.
At the same time the display MAIN: Phase reversal activ will be
triggered unless the setting is No swap.
P631
7 Settings
7-104 P631/EN M/R-11-C // P631-310-650