Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
DTOC2: IN>> PSx
076 165 077 165 078 165 079 165
Blocked 0.10 8.00 Inom
[spacer]
Setting for operate value IN>>.
[spacer]
DTOC1: IN>>> PSx
076 056 077 056 078 056 079 056
Blocked 0.10 8.00 Inom Fig. 3-94, (p. 3-129)
[spacer]
DTOC2: IN>>> PSx
076 166 077 166 078 166 079 166
Blocked 0.10 8.00 Inom
[spacer]
Setting for operate value IN>>>.
[spacer]
DTOC1: IN> dynamic PSx
076 154 077 154 078 154 079 154
1.00 0.10 8.00 Inom Fig. 3-94, (p. 3-129)
[spacer]
DTOC2: IN> dynamic PSx
076 174 077 174 078 174 079 174
1.00 0.10 8.00 Inom
[spacer]
Setting for operate value IN> in dynamic mode. This operate value is only
effective while the hold time for dynamic parameters is elapsing.
[spacer]
DTOC1: IN>> dynamic PSx
076 155 077 155 078 155 079 155
1.00 0.10 8.00 Inom Fig. 3-94, (p. 3-129)
[spacer]
DTOC2: IN>> dynamic PSx
076 175 077 175 078 175 079 175
1.00 0.10 8.00 Inom
[spacer]
Setting for operate value IN>> in dynamic mode. This operate value is only
effective while the hold time for dynamic parameters is elapsing.
[spacer]
DTOC1: IN>>> dynamic PSx
076 156 077 156 078 156 079 156
1.00 0.10 8.00 Inom Fig. 3-94, (p. 3-129)
[spacer]
DTOC2: IN>>> dynamic PSx
076 176 077 176 078 176 079 176
1.00 0.10 8.00 Inom
[spacer]
Setting for operate value IN>>> in dynamic mode. This operate value is only
effective while the hold time for dynamic parameters is elapsing.
[spacer]
DTOC1: tIN> PSx
076 060 077 060 078 060 079 060
1.00 0.00 100.00 s Fig. 3-94, (p. 3-129)
[spacer]
DTOC2: tIN> PSx
076 170 077 170 078 170 079 170
1.00 0.00 100.00 s
[spacer]
Setting for the operate delay of the IN> stage.
[spacer]
DTOC1: tIN>> PSx
076 061 077 061 078 061 079 061
0.50 0.00 100.00 s Fig. 3-94, (p. 3-129)
[spacer]
DTOC2: tIN>> PSx
076 171 077 171 078 171 079 171
0.50 0.00 100.00 s
[spacer]
Setting for the operate delay of the IN>> stage.
P631
7 Settings