EasyManua.ls Logo

Micom P631 - Page 550

Micom P631
638 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Address
Self-monitoring
SFMON: Warning (LED)
036 070
[spacer]
Warning configured for LED H3.
[spacer]
SFMON: Warning (relay)
036 100
[spacer]
Warning configured for an output relay.
[spacer]
SFMON: Warm restart exec.
041 202
[spacer]
A warm restart has been carried out.
[spacer]
SFMON: Cold restart exec.
041 201
[spacer]
A cold restart has been carried out.
[spacer]
SFMON: Cold restart
093 024
[spacer]
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Cold rest./SW update
093 025
[spacer]
A cold restart has been carried out following a software update.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Blocking/ HW failure
090 019
[spacer]
Supplementary warning that this device is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Relay Kxx faulty
041 200
[spacer]
Multiple signal: output relay defective.
Device reaction: –
'Warning' output relay: Updating
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Hardware clock fail.
093 040
[spacer]
The hardware clock has failed.
Device reaction: –
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
P631
11 Troubleshooting
11-2 P631/EN M/R-11-C // P631-310-650

Table of Contents

Related product manuals