Parameter Address
Self-monitoring
SFMON: Warning (LED)
036 070
[spacer]
Warning configured for LED H3.
[spacer]
SFMON: Warning (relay)
036 100
[spacer]
Warning configured for an output relay.
[spacer]
SFMON: Warm restart exec.
041 202
[spacer]
A warm restart has been carried out.
[spacer]
SFMON: Cold restart exec.
041 201
[spacer]
A cold restart has been carried out.
[spacer]
SFMON: Cold restart
093 024
[spacer]
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Cold rest./SW update
093 025
[spacer]
A cold restart has been carried out following a software update.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Blocking/ HW failure
090 019
[spacer]
Supplementary warning that this device is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Relay Kxx faulty
041 200
[spacer]
Multiple signal: output relay defective.
Device reaction: –
'Warning' output relay: Updating
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Hardware clock fail.
093 040
[spacer]
The hardware clock has failed.
Device reaction: –
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
P631
11 Troubleshooting
11-2 P631/EN M/R-11-C // P631-310-650