Parameter Address
[spacer]
SFMON: Battery failure
090 010
[spacer]
Battery voltage too low. Replace battery.
Device reaction: –
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Invalid SW d.loaded
096 121
[spacer]
Wrong or invalid software has been downloaded.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: +15V supply faulty
093 081
[spacer]
The +15 V internal supply voltage has dropped below a minimum value.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: +24V supply faulty
093 082
[spacer]
The +24 V internal supply voltage has dropped below a minimum value.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: -15V supply faulty
093 080
[spacer]
The −15 V internal supply voltage has dropped below a minimum value.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Wrong module slot 1
096 100
[spacer]
SFMON: Wrong module slot 2
096 101
[spacer]
SFMON: Wrong module slot 3
096 102
[spacer]
SFMON: Wrong module slot 4
096 103
[spacer]
SFMON: Wrong module slot 5
096 104
[spacer]
SFMON: Wrong module slot 6
096 105
[spacer]
SFMON: Wrong module slot 7
096 106
[spacer]
SFMON: Wrong module slot 8
096 107
[spacer]
SFMON: Wrong module slot 9
096 108
11 Troubleshooting
P631