Parameter Address
[spacer]
SFMON: Iref, b inval. range
091 008
[spacer]
The reference current determined by the P631 for differential protection is not
within the permissible range.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Matching fail. end a
091 000
[spacer]
SFMON: Matching fail. end b
091 001
[spacer]
The calculated amplitude matching factor of the differential protection function
is above the permissible range.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Ratio mtch.fact.inv.
091 004
[spacer]
The ratio of the amplitude matching factors for differential protection is not
within the permissible range.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: 2nd match.fact. inv.
091 006
[spacer]
The second highest amplitude matching factor for differential protection is
smaller than permitted.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: CTA error THRM1
098 036
[spacer]
Faulty coolant temperature acquisition.
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Setting error THRM1
098 038
[spacer]
The maximum permissible object temperature and the maximum permissible
coolant temperature have been set to the same value. This setting is not valid.
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Inv.inp.f.clock sync
093 120
[spacer]
The function was configured to a binary signal input on the analog I/O module Y.
Such a configuration is not permitted for this function.
Device reaction:
'Warning' output relay: Updating
'Blocked/faulty' output relay: –