Version Changes
Software
Note:
This version is not released for applications with IEC
61850 systems! Version -610-714 may be used as an
alternative.
MAIN
Bug fixing:
●
The sequence of MAIN: General starting (036
000) and DIFF: Trip signal (041 075) have
been changed such that starting always comes
first.
P631
‑305
‑403/404
‑610-714
Release: 2007-02-07
Hardware
No changes.
Diagram
No changes.
Software
IEC
Bug fixing:
●
The cause for a break in the client-server
communications link after approximately 49 days
for about 20 minutes has been removed. GOOSE
and GSSE were not affected by this break in the
client-server communications link.
P631
‑306
‑405/406
‑611
Release: 2007-03-15
Hardware
P631
A5 P631 Version History