Version Changes
IEC Bug fixing pertaining to the COMTRADE fault files which
a client receives via the IEC 61850 interface:
Stating of “Control Modes” in the ICD file has been
corrected. The IEC data model is not affected by this.
Bug fixing:
●
The automatically generated data file names are
now correct with fault numbers exceeding 999.
Data file names are issued according to this
format:
yyyymmdd_HHMMSS_xxx_rNNNN.eee
With: yyyy = year
mm = month
dd = day
HH = hour
MM = minute
SS = second
xxx = millisecond
r = permanent single character
NNNN = fault number
eee = file extension
In previous versions the dot (.) was overwritten
for fault numbers exceeding 999.
●
The correct number of binary channels is now
entered in the COMTRADE configuration file
(*.cfg). In the previous version the number of
binary channels was given as n*16+1 when,
because of the function configuration, n*16 binary
information signals were recorded. Therefore
values stored in the *.cfg file and the *.dat file did
not match.
LOC
Bug fixing:
●
Using the function where the set password can be
made visible on the LC-display by pressing all four
arrow keys simultaneously during the start up of
the device is now also possible with the new local
control panel (with function keys).
PSS
Bug fixing:
●
The time tags for the
spontaneous signals (according to the
communications protocol per IEC-60870-5-10x)
and the entry in the operating data memory did
not match.
A5 P631 Version History
P631
P631/EN M/R-11-C // P631-310-650 A5-17