APP - 33
APPENDICES
(4) Parameter setting of the PLC CPU (No.1)
<Screen: GX Works2
PC parameter item Description
1 No. of PLC 2 modules
2 Operating mode All station stop by stop error of PLC1/PLC2
3
Multiple CPU
synchronous startup
Check the PLC No.1/PLC No.2
4
I/O sharing when
using Multiple CPUs
Check the all CPUs can read all inputs
Not check the all CPUs can read all outputs
5
Multiple CPU high
speed communication
area setting
Use multiple CPU high speed communication
PLC
CPU specific send range
User setting area Auto refresh
point (K) I/O No. point Start End point Start End
CPU No.1 7 U3E0 7168 G10000 G17167 0 — —
CPU No.2 7 U3E1 6468 G10000 G16467 700 G16468 G17167
6 Auto refresh setting
• PLC No1
No.
Auto refresh
CPU specific
send range
point Start End Start End
1 — — — — —
2 — — — — —
3 — — — — —
• PLC No.2
No.
Auto refresh
CPU specific
send range
point Start End Start End
1 20 M2000 M2319 G16468 G16487
2 40 M2400 M3039 G16488 G16527
3 640 D0 D639 G16528 G17167