5 MANUAL CONTROL
5.4 Manual Pulse Generator Operation
185
5
Operations when stroke limit error occurs
When the hardware stroke limit error or the software stroke limit error is detected
*1
during operation, the operation will
decelerate to a stop. However, in case of "[Md.26] Axis operation status", "Manual pulse generator operation" will continue
*1
.
After stopping, manual pulse generator input pulses to the outside direction of the limit range are not accepted, but operation
can be executed within the range.
*1 Only when the current feed value or the machine feed value overflows or underflows during deceleration, the manual pulse generator
operation will terminate as "error occurring". To carry out manual pulse generator operation again, "[Cd.21] Manual pulse generator
enable flag" must be turned OFF once and turn ON.
Operation timing and processing time
The following drawing shows details of the manual pulse generator operation timing and processing time.
■RD77MS4 operation example
Normal timing time (Unit: [ms])
*1 Delays may occur in the t1 timing time due to the operation status of other axes.
Operation cycle t1
*1
t2 t3 t4
0.444 0.430 to 0.438 10.065 to 21.810 14.530 to 23.095 7.266 to 15.646
0.888 0.865 to 0.874 10.065 to 21.810 14.530 to 23.095 7.266 to 15.646
1.777 1.735 to 1.748 10.065 to 21.810 14.530 to 23.095 7.266 to 15.646
3.555 3.512 to 3.534 10.065 to 21.810 14.530 to 23.095 7.266 to 15.646
Upper/lower limit signal
ON
OFF
Manual pulse generator operation possible Manual pulse generator operation not possible
V
Manual pulse generator operation
t4
t3
Manual pulse generator
input pulses
t1
[Cd. 21] Manual pulse generator
enable flag
BUSY signal [X10,X11,X12,X13]
Start complete signal
([Md.31] Status: b14)
Standby (0) Standby (0)
[Md.26] Axis operation status
Positioning operation
The start complete signal does not turn ON in manual pulse generator operation.
001
t2
Manual pulse generator operation (4)