Command #182: Write Calibration Mode
This command writes a calibration mode number to the Ultima Gas
Monitor. The mode commands initiate a calibration sequence in the
device. Device status byte 2 can be monitored to determine the
progress of the calibration.
Request Data Bytes
BYTE FORMAT DESCRIPTION
0 Enum Calibration Mode Number (see TABLE D-11)
Response Data Bytes
BYTE FORMAT DESCRIPTION
0 Enum Calibration Mode Number (see TABLE D-11)
Command-Specific Response Codes
CODE CLASS DESCRIPTION
0 Success No Command-Specific Errors
1-2 Undefined
3 Error Parameter too large
4 Undefined
5 Error Too few data bytes
6 Undefined
7 Error In write protect mode
8-15 Undefined
16 Error Access Restricted
17-31 Undefined
32 Error Busy
33-127 Undefined