6. COMMUNICATIONS MEMORY MAP
6-46
GROUP ADDR
(hex)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT
19F5 Reactive Power Alarm Delay 2 300 1 s F2 10
19F6 Reactive Power Alarm Events 0 1 1 - FC103 0
19F7 Reactive Power Trip 0 2 1 - FC115 0
19F8 Reactive Power Trip Relays 0 3 1 - FC111 0
19F9 Positive Reactive Power Trip Level 1 25000 1 kvar F1 25
19FA Negative Reactive Power Trip Level 1 25000 1 kvar F1 25
19FB Reactive Power Trip Delay 2 300 1 s F2 10
19FC Reserved
...
1A0F Reserved
UNDER- 1A10 Block Underpower From Start 0 15000 1 s F1 0
POWER 1A11 Underpower Alarm 0 2 1 - FC115 0
1A12 Underpower Alarm Relays 0 6 1 - FC113 0
1A13 Underpower Alarm Level 1 25000 1 kW F1 2
1A14 Underpower Alarm Delay 1 30 1 s F1 1
1A15 Underpower Alarm Events 0 1 1 - FC103 0
1A16 Underpower Trip 0 2 1 - FC115 0
1A17 Underpower Trip Relays 0 3 1 - FC111 0
1A18 Underpower Trip Level 1 25000 1 kW F1 1
1A19 Underpower Trip Delay 1 30 1 s F1 1
1A1A Reserved
...
1A1F Reserved
REVERSE 1A20 Block Reverse Power From Start 0 5000 1 s F1 0
POWER 1A21 Reverse Power Alarm 0 2 1 - FC115 0
1A22 Reverse Power Alarm Relays 0 6 1 - FC113 0
1A23 Reverse Power Alarm Level 1 25000 1 kW F1 1
1A24 Reverse Power Alarm Delay 2 300 1 s F1 10
1A25 Reverse Power Alarm Events 0 1 1 - FC103 0
1A26 Reverse Power Trip 0 2 1 - FC115 0
1A27 Reverse Power Trip Relays 0 3 1 - FC111 0
1A28 Reverse Power Trip Level 1 25000 1 kW F1 1
1A29 Reverse Power Trip Delay 2 300 1 s F1 10
1A2A Reserved
1A2F Reserved
TORQUE 1A30 Torque Metering 0 1 1 N/A FC126 0
SETUP 1A30 Stator Resistance 1 50000 1 m F17 4
1A31 Pole Pairs 2 128 2 - F1 2
1A32 Torque Unit 0 1 1 - FC148 0
1A33 Reserved
1A3F Reserved