© Munters AB, 2020 51
3. Go to Climate > Ventilation and click the Extra Ventilation Tab.
4. Click
.
5. On each level, define:
o
Level: Read-only.
o
Diff: Define the temperature differential. When the temperature rises above
the target temperature by this amount at each level, Extra Ventilation begins.
Range: 0.0°C >10.0°C.
NOTE Each differential must be equal to or higher than the previous level’s differential.
o
Fan Status. Refer to Defining Basic Ventilation, page 37 on how to configure
fans.
Extra Ventilation Fan Cycle (Optional):
6. Go to System > Control Strategy > Ventilation .