8.3.4 When Connected to a PLC (FX Series) Made by Mitsubishi Electric
Corporation
Code No. Content Cause and solution
FF
Time up error
There is no response
from the PLC.
Check the wiring of the connection cable and check for
disconnection.
10
Data error
A data error occurred
during communication
Check for errors in the communication conditions settings.
12
Overrun error
The GT main unit
cannot receive data.
PLC runaway might be the problem.
61
PLC error
A NAK error has been
returned from the PLC.
Verify the PLC settings.
8.3.5 When Connected to a PLC Made by Omron Corporation
Code No. Content Cause and solution
00
Time up error
There is no response
from the PLC.
Check the wiring of the connection cable and check for
disconnection.
01
Cannot be executed
due to operation mode.
(The PLC received the
command that cannot
be executed in the
operation mode.)
Change the mode of the PLC from the operation mode to the
monitor mode.
10
Data error
A data error occurred
during communication
Check for errors in the communication conditions settings.
12
Overrun error
The GT main unit
cannot receive data.
PLC runaway might be the problem.
15
Numerical data error
Designated read/write
area is wrong.
Verify whether or not the reference device used with the basic
communication area and each part is a readable and writable
area.
• Error codes other than these are based on Omron PLC error codes.
• Be sure to used the PLC in monitor mode. Otherwise, communication will not work properly.