4-2
4.1 Connecting GT01/GT11 with PLC
4.1.1 Connecting to the TOOL port of FPΣ
ΣΣ
Σ / FP0 / FP-e (1) (Direct Connection to
GT01)
Connecting to the TOOL port
FPΣ
ΣΣ
Σ communication format settings
System register No. Item Value set
410 TOOL port unit number 1
412 Modem connection No modem connection
Data length 8 bits
Parity check Yes, Odd
Stop bits 1 bit
End code CR (Fixed)
413
Start code No STX (Fixed)
415 COM. port 1 Baud rate setting 9600 bps
Reference: <4.1.15 How to Make Communication Settings Using the FPWIN GR>
PLC communication cable: Mini-DIN 5-pin loose-wire cable (AIGT8142)
Connecting to the FPΣ
ΣΣ
Σ/FP0/FP-e TOOL port
Note:
• Keep the cable no longer than 3 m.
• In case of connecting to PLC with all expansion slots used, prepare an external 5 V DC power supply
for the GT01 due to current consumption limits.