4-3
4.1.2 Connecting to the TOOL port of FPΣ
ΣΣ
Σ / FP0 / FP-e (2)
Connecting to the TOOL port
FPΣ
ΣΣ
Σ communication format settings
System register No. Item Value set
410 TOOL port unit number 1
412 Modem connection No modem connection
Data length 8 bits
Parity check Yes, Odd
Stop bits 1 bit
End code CR (Fixed)
413
Start code No STX (Fixed)
415 COM. port 1 Baud rate setting 9600 bps
Reference: <4.1.15 How to Make Communication Settings Using the FPWIN GR>
PLC communication cable: Mini-DIN 5-pin loose-wire cable (AIGT8162, AIGT8165, AIGT8160)
Connecting to the FPΣ
ΣΣ
Σ/FP0/FP-e TOOL port