3.47 EDH0162En1040 – 06/99
MM4005 EO — Automatical execution on power on
Usage IMM PGM MIP
Syntax xxEOnn or EO?
Parameters
Description xx
[int] — Program number to execute on power on.
nn [int] — Number of times on execution.
? — Read program number to execute and number of times
of execution.
Range xx — 1 to 127.
nn
— 1 to 2147385345.
Units xx — None.
nn — None.
Defaults xx Missing: 0 (no program execution on power on).
Out of range: Error F.
Floating point: Error A.
nn Missing: 1 (one time of execution).
Out of range: Error C.
Description This command sets the program number that is automatically executed on
power on. If xx is zero or missing, no program is executed. If nn is missing,
the xx numbered program is executed one time.
Returns If the sign “?” takes place of the nn value and xx missing, this command
reportes the number of the program that is executed on power on and
number of times of execution.
Errors A — Unknown message code.
C — Parameter out of limits.
F — Program number incorrect.
Rel. Commands EX — Execute a program.
Example 2EO | Set program #2 to be executed one time on power on.
EO? | Read executed on power on program number.
EO, 2, 1 | Controller tells the program #2 to be executed one time on power
on.
EO | Reset automatical execution - no program is executed on power on.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com