3.53 EDH0162En1040 – 06/99
MM4005 FB — Label function key
Usage IMM PGM MIP
Syntax xxFBaa
Parameters
Description xx
[int] — Function key number.
aa [chaîne] — Label to be displayed.
Range xx — 1 to 4.
aa
— 0 to 6 characters.
Units xx — None.
aa — None.
Defaults xx Missing: Error O.
Out of range: Error O.
Floating point: Error A.
aa Missing: Clears the selected function key label.
Out of range: Truncates label to the first 6 characters.
Description This command allows the user to define a label for a function key. Using
the FD or WF command will display the use-defined function keys.
For the
xx value, the four function keys are numbered from 1 to 4, from left
to right.
NOTE
The command is valid only in programming mode, where the function
keys are not used by the normal operation of the controller.
Returns
None.
Errors A — Unknown message code.
J — Command authorized only in programming mode.
O — Variable number out of range.
Rel. Commands FC — Clear function key line.
FD — Display function keys.
WF — Wait for function key.
Example 3XX | Clear program #3 from memory, if any.
3EP | Activate program mode and enter following commands as program
#3.
4FBSTOP | Define custom label for function key #4 as STOP.
… |
… |
… |
7WF |
Display the custom function key label(s) (STOP), wait for a valid
function key to be pressed and put its ASCII code in variable #7.
FC | Clear function key display line.
… |
… |
… |
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com