If no problem is found during no-load run, connect the mechanical system and run the inverter with load 
via the Digital Operator. 
 
⚫
 
Mechanical system connection 
Make sure that the motor stopped completely before connecting the mechanical system. 
Then, connect the mechanical system with the motor securely to prevent the screws from loosening. 
 
⚫
 
Operation via Digital Operator 
In case of abnormal inverter run, be prepared to press the STOP/RESET key   on the Digital 
Operator. 
In the same way as you did during no-load run, stop the machine via the Digital Operator. 
 
⚫
 
RUN mode checks 
Start with a low speed and, while checking that the machine moves smoothly in a correct direction, 
increase the Output Frequency Setting/Monitor (F001) value. 
Check that there is no mechanical vibration and noise by varying the Output Frequency Setting/ 
Monitor (F001) and RUN Direction Selection (F004) settings. 
Also, check a current, load rate, and voltage by the Output Current Monitor (d002), Electronic Ther- 
mal Load Rate Monitor (d104), and DC Voltage Monitor (d102). 
Check that the output current is up to 150% of the motor rated current. 
Also, check that the electronic thermal load rate is sufficiently low to reach 100%. 
Check that the main circuit DC voltage for 200-V class and for 400-V class is sufficiently low to reach 
390 VDC and 780 VDC, respectively. 
 
 
To operate the inverter with only basic parameters, refer to Section 5 Basic Settings. 
To use applied functions such as sensorless vector control, V/f control with speed feedback, torque 
control, and simple position control, in addition to Section 5 Basic Settings, refer to Section 6 Vector 
Control and Applied Functions.