4 Parameter List
4 - 18
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Torque
limit
b040
Torque Limit Selection
00: Four-quadrant separate setting
01: Terminal switching
02: Analog voltage input
03: Option (No applicable Option)
00
Enabled
P. 6-12
b041
Torque Limit 1 (Four-
quadrant Mode For-
ward Power Run-
ning)
0. to 200.
255: no (Torque limit disabled)
200.
Enabled
%
b042
Torque Limit 2 (Four-
quadrant Mode
Reverse Regenera-
tion)
200.
Enabled
b043
Torque Limit 3 (Four-
quadrant Mode
Reverse Power Run-
ning)
200.
Enabled
b044
Torque Limit 4 (Four-
quadrant Mode For-
ward Regeneration)
200.
Enabled
b045
Torque LADSTOP
Selection
00: Disabled
01: Enabled
00
Enabled
P. 6-14
b046
Reverse Rotation
Prevention Selection
00: Disabled
01: Enabled
00
Enabled
P. 6-11
Mode
b049
Heavy load/Light
Load Selection
00: Heavy load mode (CT)
01: Light load mode (VT)
00
Disabled
P. 5-11
Deceleration
Stop on Power
Interruption
b050
Deceleration Stop
Selection on Power
Interruption
00: Disabled
01: Enabled (Deceleration stop)
02: Enabled (Constant voltage, without
recovery)
03: Enabled (Constant voltage, with
recovery)
00
Disabled
P. 7-69
b051
Starting Voltage on
Power Interruption
200-V class: 0.0 to 400.0
400-V class: 0.0 to 800.0
220.0/
440.0
Enabled
V
b052
Deceleration Hold
Level on Power Inter-
ruption
200-V class: 0.0 to 400.0
400-V class: 0.0 to 800.0
360.0/
720.0
Enabled
V
b053
Deceleration Time on
Power Interruption
0.01 to 3600.00
1.00
Enabled
s
b054
Deceleration Starting
Width on Power
Interruption
0.00 to 10.00 (100.00)
*1
0.00
Enabled
Hz