8 Communications Functions
8 - 65
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Param-
eter
No.
R/W
Monitor or setting data
Data
resolution
Page
1334
hex
1333 hex
Deceleration Stop
Selection on
Power Interruption
b050
R/W
00: Disabled
01: Enabled (Deceleration
stop)
02: Enabled (Constant volt-
age, without recovery)
03: Enabled (Constant volt-
age, with recovery)
P. 7-69
1335
hex
1334 hex
Starting Voltage
on Power Interrup-
tion
b051
R/W
200-V class: 0 to 4000
400-V class: 0 to 8000
0.1 [V]
1336
hex
1335 hex
Deceleration Hold
Level on Power
Interruption
b052
R/W
200-V class: 0 to 4000
400-V class: 0 to 8000
0.1 [V]
1337
hex
1336 hex
Deceleration Time
on Power
Interruption
b053
(HIGH)
R/W
1 to 360000
0.01 [s]
1338
hex
1337 hex
b053
(LOW)
R/W
1339
hex
1338 hex
Deceleration
Starting Width on
Power Interruption
b054
R/W
0 to 10000
0.01
[Hz]
133A to
133E
hex
Reserved
133F
hex
133E hex
Window
Comparator O
Upper Limit Level
b060
R/W
0. to 100.
(Lower limit: b061 + b062 2)
1 [%]
P. 7-90
1340
hex
133F hex
Window
Comparator O
Lower Limit Level
b061
R/W
0. to 100.
(Upper limit: b060 b062 2)
1 [%]
1341
hex
1340 hex
Window
Comparator O
Hysteresis Width
b062
R/W
0. to 10.
(Upper limit: (b060 b061) /
2)
1 [%]
1342
hex
1341 hex
Window
Comparator
OI
Upper Limit Level
b063
R/W
0. to 100.
(Lower limit: b064 + b065 2)
1 [%]
1343
hex
1342 hex
Window
Comparator
OI
Lower Limit Level
b064
R/W
0. to 100.
(Upper limit: b063 b065 2)
1 [%]
1344
hex
1343 hex
Window
Comparator OI
Hysteresis Width
b065
R/W
0. to 10.
(Upper limit: (b063 b064) /
2)
1 [%]
8
8-9 Modbus Communication Data Lists
8-9-4 Group A/b/C/H/P Register List