8 Communications Functions
8 - 66
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1345
to
1348
hex
Reserved
1349
hex
1348 hex
Analog Operation
Level at O
Disconnection
b070
R/W
0 to 100
255: no (Disabled)
1 [%]
P. 7-90
134A
hex
1349 hex
Analog Operation
Level at OI
Disconnection
b071
R/W
0 to 100
255: no (Disabled)
1 [%]
134B to
134D
hex
Reserved
134E
hex
134D hex
Ambient
Temperature
b075
R/W
10 to 50
1 [°C]
P. 7-87
134F to
1350
hex
Reserved
1351
hex
1350 hex
Integrated Power
Clear
b078
R/W
00: Clear disabled
01: Executes Clear
(Resets to 00 after
execution.)
P. 7-9
1352
hex
1351 hex
Integrated Power
Display Scale
b079
R/W
1 to 1000
1
1353
hex
Reserved
1354
hex
1355
hex
1354 hex
Starting Frequency
b082
R/W
1 to 1000 (10000)
*1
0.01
[Hz]
P. 7-35
1356
hex
1355 hex
Carrier Frequency
b083
R/W
20 to 150 (100)
*1
0.1
[kHz]
P. 7-31
1357
hex
1356 hex
Initialization
Selection
b084
R/W
00: Initialization dis-
abled
01: Clearing fault mon-
itor
02: Initialize data
03: Clear fault monitor
+ Initialize data
04:
Clear fault monitor
+
Initialize
data
+
Clear
DriveProgramming
P. 5-5
1358
hex
1357 hex
Initialization Data
Selection
b085
R/W
Do not change the
default 00.
1359
hex
1358 hex
Frequency
Conversion
Coefficient
b086
R/W
1 to 9999
0.01
P. 7-6
135A
hex
1359 hex
STOP Key Selection
b087
R/W
00: Enabled
01: Disabled
02: Only RESET
enabled
P. 5-41
135B
hex
135A hex
Free-run Stop
Selection
b088
R/W
00: 0-Hz restart
01: Frequency pull-in
restart at shutoff
02: Frequency pull-in
restart
P. 5-38

Table of Contents