8 Communications Functions
8 - 98
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
2253
to
2268
hex
Reserved
2269
hex
2268 hex
2nd AVR Selection
A281
R/W
00: Always ON
01: Always OFF
02: OFF during decel-
eration
P. 7-42
226A
hex
2269 hex
2nd Motor Rated
Voltage Selection
A282
R/W
200-V class:
00 (200)
01 (215)
02 (220)
03 (230)
04 (240)
400-V class:
05 (380)
06 (400)
07 (415)
08 (440)
09 (460)
10 (480)
P. 5-20
P. 7-42
226B to
226E
hex
Reserved
226F
hex
226E hex
2nd Acceleration
Time 2
A292
(HIGH)
R/W
1 to 360000
0.01 [s]
P. 5-36
2270
hex
226F hex
A292
(LOW)
R/W
2271
hex
2270 hex
2nd Deceleration
Time 2
A293
(HIGH)
R/W
1 to 360000
0.01 [s]
2272
hex
2271 hex
A293
(LOW)
R/W
2273
hex
2272 hex
2nd 2-step
Acceleration/
Deceleration
Selection
A294
R/W
00: Switch via 2CH ter-
minal
01: Switch by 2-step
Accelera-
tion/Deceleration
Frequency
02: Switch only during
forward/reverse
switching
2274
hex
2273 hex
2nd 2-step
Acceleration
Frequency
A295
(HIGH)
R/W
0 to 59000
0.01
[Hz]
2275
hex
2274 hex
A295
(LOW)
R/W
2276
hex
2275 hex
2nd 2-step
Deceleration
Frequency
A296
(HIGH)
R/W
0 to 59000
0.01
[Hz]
2277
hex
2276 hex
A296
(LOW)
R/W
2278 to
230B
hex
Not used
Not accessible

Table of Contents