8 Communications Functions
8 - 99
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
230C
hex
230B hex
2nd Electronic
Thermal Level
b212
R/W
200 to 1000
0.1 [%]
P. 5-15
230D
hex
230C hex
2nd Electronic
Thermal
Characteristics
Selection
b213
R/W
00: Reduced torque
characteristics
01: Constant torque
characteristics
02: Free setting
230E to
2315
hex
Reserved
2316
hex
2315 hex
2nd Overload Limit
Selection
b221
R/W
00: Disabled
01: Enabled during
acceleration and
constant speed
02: Enabled during
constant speed
03: Enabled during
acceleration and
constant speed
(Accelerated
during regenera-
tion)
P. 7-78
2317
hex
2316 hex
2nd Overload Limit
Level
b222
R/W
100 to 2000 (1500)
0.1 [%]
2318
hex
2317 hex
2nd Overload Limit
Parameter
b223
R/W
1 to 30000
0.1 [s]
2319
to
2428
hex
Not used
Not accessible
2429
hex
2428 hex
2nd Overload
Warning Level
C241
R/W
0 to 2000
0.1 [%]
P. 7-78
242A to
2501
hex
Not used
Not accessible
2502
hex
2501 hex
2nd Motor Parame-
ter Selection
H202
R/W
00: Standard motor
parameter
02: Auto-tuning param-
eter
P. 6-4
2503
hex
2502 hex
2nd Motor Capacity
H203
R/W
00: 0.1
01: 0.2
02: 0.4
03: 0.55
04: 0.75
05: 1.1
06: 1.5
07: 2.2
08: 3.0
09: 3.7
10: 4.0
11: 5.5
12: 7.5
13: 11.0
14: 15.0
15: 18.5
8
8-9 Modbus Communication Data Lists
8-9-5 2nd Control Register Number List

Table of Contents