Function Tables Section 1-8
Managing the 
Cycle Time
Reducing the cycle time. • Use tasks to put parts of the pro-
gram that don’t need to be executed
into “standby” status.
• Use JMP(004) and JME(005) to
jump parts of the task that don’t
need to be executed.
• Convert parts of the task to subrou-
tines if they are executed only under
particular conditions.
• Disable a Unit’s Special I/O Unit
refreshing in the PLC Setup if it isn’t
necessary to exchange data with
that Special I/O Unit every cycle.
• Setting index and data registers to
be shared by all tasks when these
registers are not being used. 
Programming 
Manual 
(W394)
6-1 Cycle 
Time/High-
speed Pro-
cessing
Setting a fixed (minimum) 
cycle time.
• Variations in I/O 
response times can be 
eliminated by suppress-
ing processing variations.
Set a minimum cycle time in the PLC 
Setup.
Setting a maximum cycle 
time. 
(Generating an error for a 
cycle time exceeding the 
maximum.)
Set a maximum cycle time (watch 
cycle time) in the PLC Setup. If the 
cycle time exceeds this value, the 
Cycle Time Too Long Flag (A40108) 
will be turned ON and PLC operation 
will be stopped.
Operation 
Manual
7-1 PLC 
Setup
Reducing the I/O response 
time for particular I/O 
points.
Use immediate refreshing or 
IORF(097).
Programming 
Manual 
(W394)
6-1 Cycle 
Time/High-
speed Pro-
cessing
Finding I/O refresh times 
for individual Units
--- Operation 
Manual
 Parallel 
Processing 
Mode (CJ-H 
CPU Units 
Only)
Studying the I/O response 
time
--- 10-4-6 I/O 
Response 
Time
Finding the increase in the 
cycle time for online editing
--- 10-4-5 
Online Edit-
ing Cycle 
Time Exten-
sion
Purpose Function Manual Reference