PLC Setup Section 7-1
Execution Settings
Startup Condition (CJ1-H CPU Units Only)
Note This setting applies only to specific Units. If “don’t wait” is set, the CPU Unit
will not wait only for those specific Units, i.e., it will still wait for all other Units
to start.
7-1-2-2 CPU Settings Tab Page
Execute Process
Detect Low Battery
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+83 15 0: Wait for Units.
1: Don’t wait.
Default: 0
To start the CPU Unit in MONITOR or PRO-
GRAM mode even if there is one or more
Units that has not completed startup pro-
cessing, set this setting to 1 (Don’t wait for
Units).
To wait for all Units to finish startup process-
ing, set this setting to 0 (Wait for Units).
--- At startup
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+128 15 0: Detect
1: Do not detect
Default: 0
This setting determines whether CPU Unit
battery errors are detected. If this setting is
set to 0 and a battery error is detected, the
ERR/ALM indicator on the CPU Unit will
flash and the Battery Error Flag (A40204)
will be turned ON, but CPU Unit operation
will continue.
A40204 (Bat-
tery Error
Flag)
At the next
cycle.