88
Specifications Section 2-1
2-1-2 General Specifications
Sched-
uled
inter-
rupts
Scheduled interrupts
in units of 0.1 ms
Starts scheduled interrupt tasks with a minimum inter-
val of 0.5 ms, at a precision of 0.1 ms. (Set in the PLC
Setup.)
Programming Manual:
6-5 Using a Scheduled Inter-
rupt as a High-speed Timer
Reset start by MSKS
instruction
When MSKS is executed, reset starts the internal timer
and standardizes the time to first interrupt.
Internal timer PV
reading by MSKS
instruction
When MSKS is executed, reads the time elapsed from
the start of the scheduled interrupt or the previous
scheduled interrupt.
Item Specifications
Power Supply Unit CJ1W-PA205R CJ1W-PA205C CJ1W-PA202 CJ1W-PD025 CJ1W-PD022
Supply voltage 100 to 240 V AC (wide-range), 50/60 Hz 24 V DC
Operating voltage and
frequency ranges
85 to 264 V AC, 47 to 63 Hz 19.2 to 28.8 V DC 21 to 26.4 V DC
Power consumption 100 VA max. 50 VA max. 50 W max. 35 W max.
Inrush current
(See note 3.)
At 100 to 120 V AC:
15 A/8 ms max. for cold start
At 200 to 240 V AC:
30 A/8 ms max. for cold start
At 100 to 120 V AC:
20 A/8 ms max. for
cold start
At 200 to 240 V AC:
40 A/8 ms max. for
cold start
At 24 V DC:
30 A/20 ms max. for
cold start
At 24 V DC:
30 A/20 ms max. for
cold start
Output capacity
(See note 7.)
5.0 A, 5 V DC (including supply to CPU
Unit)
2.8 A, 5 V DC
(including supply to
CPU Unit)
5.0 A, 5 V DC
(including supply to
CPU Unit)
2.0 A, 5 V DC
(including supply to
CPU Unit)
0.8 A, 24 V DC
Tota l: 2 5 W max .
0.4 A, 24 V DC
Total: 14 W max.
0.8 A, 24 V DC
Total: 25 W max.
0.4 A, 24 V DC
Total: 19.6 W max.
Output terminal (ser-
vice supply)
Not provided
RUN output
(See note 2.)
Contact configura-
tion: SPST-NO
Switch capacity:
250 V AC, 2 A (resis-
tive load)
120 V AC, 0.5 A
(inductive load), 24 V
DC, 2A (resistive
load)
24 V DC, 2 A (induc-
tive load)
Not provided.
Replacement notifica-
tion function
Not provided. With
Alarm output (open-
collector output)
30 VDC max., 50 mA
max.
Not provided.
Insulation resistance 20 M
min. (at
500 V DC) between
AC external and GR
terminals
(See note 1.)
20 M
min. (at 500 V
DC) between all
external terminals and
GR terminal, and
between all alarm out-
put terminals.
20 M
min. (at 250 V
DC) between all
alarm output termi-
nals and GR terminal.
20 M
min. (at
500 V DC) between
AC external and GR
terminals
(See note 1.)
20 M
min. (at
500 V DC) between
DC external and GR
terminals (See note
1.)
--- (See note 6.)
Dielectric strength 2,300 V AC 50/60 Hz
for 1 min between
AC external and GR
terminals (See notes
1 and 5.)
Leakage current:
10 mA max.
2,300 V AC, 50/60 Hz
for 1 minute between
all external terminals
and GR terminal and
between all alarm
output terminals with
a leakage current of
10 mA max.
2,300 V AC 50/60 Hz for 1 min between AC
external and GR terminals
Leakage current: 10 mA max.
--- (See note 6.)
1,000 V AC 50/60 Hz
for 1 min between
AC external and GR
terminals (See notes
1 and 5.)
Leakage current:
10 mA max.
1,000 V AC, 50/60 Hz
for 1 minute between
all alarm output ter-
minals and GR termi-
nal with a leakage
current of 10 mA
max.
1,000 V AC 50/60 Hz for 1 min between AC
external and GR terminals
Leakage current: 10 mA max.