307
PLC Setup Section 7-1
7-1-2-7 Peripheral Port Tab Page
The following settings are valid when pin 4 on the DIP switch on the CPU Unit
is ON.
Host Link Settings
Communications Settings
Mode: Communications Mode
Format: Data Bits
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+144 15 0: Standard*
1: PLC Setup (Cus-
tom)
Default: 0
*The default settings are for 1 start bit, 7
data bits, even parity, 2 stop bits, and a baud
rate of 9,600 bps.
A61901
(Peripheral
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+144 8 to 11 00: Host Link
05: Host link
Default: 0
This setting determines whether the periph-
eral port will operate in host link mode or
another serial communications mode. (Host
link can be specified with 00 or 05.)
The Peripheral Bus Mode is for communica-
tions with Programming Devices other than
the Programming Console.
A61901
(Peripheral
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+144 3 0: 7 bits
1: 8 bits
Default: 0
These settings are valid only when the com-
munications mode is set to Host link.
These settings are also valid only when the
Peripheral Port Settings Selection is set to
1: PLC Setup.
A61901
(Peripheral
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)