519
Error Processing Section 11-2
11-2-8 Program Error Check
ON
OFF
#FFFF
ON
OFF
ON
OFF
Program error occurred.
A29512 (Task
Error Flag) ON?
A29511 (No END
Flag) ON?
A29508 to A29510
(instruction error
flags) ON?
Task that stopped
program (A294)?
An active task does not exist. Check
the usage of TKON(820) and
TKOF(821).
An attempt was made to start a task that
doesn’t exist. Check the MSKS(690)
instruction used to enable the interrupt task
of the specified number.
An attempt was made to start the task of the
specified number with an interrupt. Check
the CPU Bus Unit.
There is no END(001) in the task
that stopped the program (A294).
Add END(001).
The program was stopped for the PLC
Setup setting to stop the program for
instruction errors. Check the program
based on the task (A294) and address
(A298 and A299) that stopped the program.
Turn the power supply OFF and then back
ON again.
#8002, #8003,
#8064 to #8083
Not related
to problem.