311
PLC Setup Section 7-1
Baud Rate (bps)
Response Monitoring Time
7-1-2-8 Peripheral Service Tab Page (CPU Processing Mode Settings)
Peripheral Service Mode (Peripheral Servicing Priority Mode)
Instruction Execution Time
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+145 0 to 7 00: 9,600
01: 300
02: 600
03: 1,200
04 2,400
05: 4,800
06: 9,600
07: 19,200
08: 38,400
09: 57,600
0A: 115,200
Default: 00
These setting is valid only when the commu-
nications mode is set to Host Link.
These settings are also valid only when the
Peripheral Port Settings Selection is set to
1: PLC Setup.
A61901
(Peripheral
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+151 8 to 15 00: 5 s
01 to FF: 100 to
25,500 ms (Unit:
100 ms)
Default: 00
Monitors the time from when the FINS com-
mand is converted into CompoWay/F using
Serial Gateway and sent until the response
is received.
Default: 5 s; PLC Setup: 0.1 to 25.5 s
Note: If a timeout occurs, the FINS end
code 0205 hex (response timeout) will be
returned to the FINS source.
A61901
(Peripheral
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+219 08 to 15 00
05 to FF (hex)
Default: 00 (hex)
The Peripheral Servicing Priority Mode will
be used if a time slice is set for instruction
execution (5 to 255 ms in 1-ms increments).
Instructions will be executed at the set time
slice.
00: Disable priority servicing
05 to FF: Time slice for instruction execution
(5 to 255 ms in 1-ms increments)
A266 and
A267
At start of
operation
(Can’t be
changed dur-
ing opera-
tion.)