EasyManua.ls Logo

Omron CJ - 08-2008 - Introduction

Omron CJ - 08-2008
733 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
210
Introduction Section 4-1
4-1 Introduction
The following procedure outlines the recommended steps to follow when pre-
paring CJ-series PLCs for operation.
1,2,3... 1. Installation
Set the DIP switches on the front of each Unit as required.
Connect the CPU Unit, Power Supply Unit, I/O Units, and End Cover. In-
stall a Memory Card if required.
See
5-2 Installation for details.
2. Wiring
Connect the power supply wiring, I/O wiring, and Programming Device
(CX-Programmer or Programming Console). Connect communications
wiring as required.
See
5-3 Wiring for details on power supply and I/O wiring.
3. Initial Settings (Hardware)
Set the DIP switches and Rotary switches on the CPU Unit and other Units.
4. Confirming Programming Device Connection
a) Connect a Programming Device (i.e., the CX-Programmer or a Pro-
gramming Console).
b) Check the power supply wiring and voltage, turn ON the power supply,
and check to be sure the Programming Device will connect to the CPU
Unit.
See
3-3 Programming Devices for details.
5. Registering the I/O Tables (If Required.)
Check the Units to verify that they are installed in the right slots. With the
PLC in PROGRAM mode, register the I/O tables from the CX-Programmer
(online) or Programming Console. (Another method is to create the I/O ta-
bles in CX-Programmer (offline) and transfer them to the CPU Unit.)
See
8-1 I/O Allocations for details.
6. PLC Setup Settings
With the PLC in PROGRAM mode, change the settings in the PLC Setup
as necessary from the CX-Programmer (online) or Programming Console.
(Another method is to change the PLC Setup in CX-Programmer (offline)
and transfer it to the CPU Unit.)
7. DM Area Settings
a) Use a Programming Device (CX-Programmer or Programming Con-
sole) to make any necessary settings in the parts of the DM Area that
are allocated to Special I/O Units and CPU Bus Units.
b) Reset the power (ON
OFF ON) or toggle the Restart Bit for each
Unit. See the Unit’s operation manual for details.
8. Writing the Program
Write the program with a Programming Device (CX-Programmer or Pro-
gramming Console).
9. Transferring the Program (CX-Programmer Only)
With the PLC in PROGRAM mode, transfer the program from CX-Pro-
grammer to the CPU Unit.

Table of Contents

Related product manuals