351
Creating I/O Tables Section 8-2
User-set I/O Allocations
8-2-2 Procedures for Registering I/O Tables
I/O Table Registration with
CX-Programmer
Use the following procedure to register the I/O tables with the CX-Program-
mer.
1,2,3... 1. Double-click IO Table in the project tree in the main window. The I/O Table
Window will be displayed.
2. Select Options and then Create. The models and positions of the Units
mounted to the Racks will be written to the CPU Unit as the registered I/O
tables.
The I/O tables can also be edited offline and then transferred to the CPU Unit.
1,2,3... 1. Double-click IO Table in the project tree in the main window. The I/O Table
Window will be displayed.
2. Double-click Rack to be edited. The slots for the selected Rack will be dis-
played.
3. Right-click the slot to which a Unit is to be assigned and select the Unit
from the pull-down menu.
4. After editing the I/O tables, transfer them to the CPU Unit by selecting Op-
tions - Transfer to PLC.
I/O Table Registration with
a Programming Console
A Programming Console can be used to automatically register the I/O tables
in the CPU Unit according to the Units actually mounted in the PLC. With a
Programming Console, words cannot be reserved and first words cannot be
set for Racks or slots. Use the following procedure to create I/O tables with a
Programming Console.
Creating I/O Tables
CX-Programmer
OR
Operation performed to
create I/O tables.
Programming Console
Units connected
when power is turned
ON are registered in
CPU Unit.
Editing and Downloading I/O Tables
CX-Programmer
Edited I/O tales
Registered I/O tables
Down-
loading
CPU Rack
00 16pt Input Unit
01 16pt Input Dummy
02 32pt Output Unit
Rack 01
Registered I/O tables
Transferring Parameter File to CPU Unit
File memory (Memory
Card or EM Area)
Registered I/O tables
CPU Rack
00 16pt
01
02
Rack 01
I/O tables in
parameter file
CLR
000000 CT00
FUN SHIFT
CH
*DM
000000 I/O TBL ?