263
Wiring Section 5-3
The terminals have screws with self-raising pressure plates. Connect the
lead wires to the terminals as shown below.
Terminal Blocks The I/O Units are equipped with removable terminal blocks. The lead wires do
not have to be removed from the terminal block to remove it from an I/O Unit.
5-3-3 Wiring I/O Units with Connectors
This section describes wiring for the following Units:
CJ-series Basic I/O Units with Connectors (32- and 64-point Units)
CJ-series Basic I/O Units with connectors use special connectors to connec-
tor to external I/O devices. The user can combine a special connector with
cable or use a preassembled OMRON cable to connect to a terminal block or
I/O Terminal. The available OMRON cables are described later in this section.
Be sure not to apply a voltage that exceeds the input voltage for Input
Units or the maximum switching capacity for Output Units.
When the power supply has positive and negative terminals, be sure to
wire them correctly. Loads connected to Output Units may malfunction if
the polarity is reversed.
Use reinforced insulation or double insulation on the DC power supply
connected to DC I/O Units when required by EC Directives (low voltage).
When connecting the connector to the I/O Unit, tighten the connector
screws to a torque of 0.2 N·m.
Turn on the power after checking the connector’s wiring. Do not pull the
cable. Doing so will damage the cable.
Bending the cable too sharply can damage or break wiring in the cable.
17.5 mm
Screw (M3 screw with
self-raising pressure plate)
O
D
21
1
Terminal block leve
r
CJ-series Basic I/O Unit