25
CJ1-H/CJ1M CPU Unit Ver. 4.0 Upgrades Section 1-4
1-4 CJ1-H/CJ1M CPU Unit Ver. 4.0 Upgrades
This section summarizes the upgrades made for CJ1-H/CJ1M CPU Units with
unit version 4.0. CX-Programmer version 7.0 or higher must be used to
enable using the following functions.
Functional Upgrades for Unit Version 4.0
1-4-1 Online Editing of Function Blocks
Unit Version 3.0 or Earlier Function block definitions could not be changed during operation.
Unit Version 4.0 or Later Function block definitions can be changed during operation. This allows func-
tion block definitions to be quickly corrected during debugging. It also allows
function blocks to be used more easily in systems that operate 24 hours a day.
1-4-2 Input-Output Variables in Function Blocks
Unit Version 3.0 or Earlier The data size of parameters that could be passed to and from function blocks
was limited to four words maximum. It was thus necessary to separate ele-
ments with large data sizes, such as data tables.
Unit Version 4.0 or Later Input-output variables can be used to passed large quantities of data, such as
table data.
Function Section
Online Editing of Function Blocks 1-4-1 Online Editing of Function
Blocks
Input-Output Variables in Function Blocks 1-4-2 Input-Output Variables in
Function Blocks
Text String Support in Function Blocks 1-4-3 Text String Support in
Function Blocks
Pattern A
Pattern B
Pattern C
Pattern D
Pattern E
D100
D101
D102
D103
D104
D100
D101
D102
D103
D104
FB
(INT) (INT)
Para1i Para1o
(INT) (INT)
Para2i Para2o
(INT) (INT)
Para3i Para3o
(INT) (INT)
Para4i Para4o
(INT) (INT)
Para5i Para5o
D100
D101
D102
D103
D104
Pattern A
Pattern B
Pattern C
Pattern D
Pattern E
D100
D101
D102
D103
D104
D100
FB
(INT)[]
Para1 --- Para1
D10
0