475
Instruction Execution Times and Number of Steps Section 10-5
Note 1. When a double-length operand is used, add 1 to the value shown in the
length column in the following table.
2. Supported only by CPU Units Ver. 2.0 or later.
10-5-4 Timer and Counter Instructions
CONDITIONAL
JUMP NOT
CJPN 511 2 0.31 0.38 0.48 8.5 0.95 0.95 When JMP condi-
tion is satisfied
MULTIPLE JUMP JMP0 515 1 0.048 0.06 0.06 0.12 0.15 0.15 ---
MULTIPLE JUMP
END
JME0 516 1 0.048 0.06 0.06 0.12 0.15 0.15 ---
FOR LOOP FOR 512 2 0.18 0.21 0.21 0.21 1.00 1.00 Designating a con-
stant
BREAK LOOP BREAK 514 1 0.048 0.12 0.12 0.12 0.15 0.15 ---
NEXT LOOP NEXT 513 1 0.14 0.18 0.18 0.18 0.45 0.45 When loop is contin-
ued
0.18 0.22 0.22 0.22 0.55 0.55 When loop is ended
Instruction Mnemonic Code Length
(steps)
(See
note 1.)
ON execution time (
µs) Conditions
CPU6@H-R CPU6@HCPU4@HCPU4@ CJ1M
excluding
CPU11/21
CJ1M
CPU11/21
Instruction Mnemonic Code Length
(steps)
(See
note 1.)
ON execution time (
µs) Conditions
CPU6@H-R CPU6@HCPU4@HCPU4@ CJ1M
excluding
CPU11/21
CJ1M
CPU11/21
HUNDRED-MS
TIMER
TIM --- 3 0.45 0.56 0.88 0.42 1.30 1.30 ---
TIMX 550 0.45
TEN-MS TIMER TIMH 015 3 0.70 0.88 1.14 0.42 1.80 1.80 ---
TIMHX 551 0.46 0.56 0.88 0.42 1.30 1.30
ONE-MS TIMER TMHH 540 3 0.69 0.86 1.12 0.42 1.75 1.75 ---
TMHHX 552 0.46 0.56 0.88 0.42 1.30 1.30
TENTH-MS TIMER
(See note 2.)
TIMU 541 3 0.45 --- --- --- --- --- ---
TIMUX 556 0.45
HUNDREDTH-MS
TIMER (See
note 2.)
TMUH 544 3 0.45 --- --- --- --- --- ---
TMUHX 557 0.45
ACCUMULATIVE
TIMER
TTIM 087 3 16.1 16.1 17.0 21.4 27.4 30.9 ---
10.9 10.9 11.4 14.8 19.0 21.2 When resetting
8.5 8.5 8.7 10.7 15.0 16.6 When interlocking
TTIMX 555 16.1 16.1 17.0 21.4 27.4 --- ---
10.9 10.9 11.4 14.8 19.0 --- When resetting
8.5 8.5 8.7 10.7 15.0 --- When interlocking
LONG TIMER TIML 542 4 7.6 7.6 10.0 12.8 16.3 17.2 ---
6.2 6.2 6.5 7.8 13.8 15.3 When interlocking
TIMLX 553 7.6 7.6 10.0 12.8 16.3 --- ---
6.2 6.2 6.5 7.8 13.8 --- When interlocking
MULTI-OUTPUT
TIMER
MTIM 543 4 20.9 20.9 23.3 26.0 38.55 43.3 ---
5.6 5.6 5.8 7.8 12.9 13.73 When resetting
MTIMX 554 20.9 20.9 23.3 26.0 38.55 --- ---
5.6 5.6 5.8 7.8 12.9 --- When resetting
COUNTER CNT --- 3 0.51 0.56 0.88 0.42 1.30 1.30 ---
CNTX 546 0.51 ---
REVERSIBLE
COUNTER
CNTR 012 3 16.9 16.9 19.0 20.9 31.8 27.2 ---
CNTRX 548 ---
RESET TIMER/
COUNTER
CNR 545 3 9.9 9.9 10.6 13.9 14.7 17.93 When resetting 1
word
4.16 ms 4.16 ms 4.16 ms 5.42 ms 6.21 ms 6.30 ms When resetting
1,000 words
CNRX 547 9.9 9.9 10.6 13.9 14.7 17.93 When resetting 1
word
4.16 ms 4.16 ms 4.16 ms 5.42 ms 6.21 ms 6.30 ms When resetting
1,000 words