EasyManua.ls Logo

Omron CJ - 08-2008 - File Memory Instructions; Network Instructions; Serial Communications Instructions

Omron CJ - 08-2008
733 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
490
Instruction Execution Times and Number of Steps Section 10-5
10-5-22 Serial Communications Instructions
Note When a double-length operand is used, add 1 to the value shown in the length
column in the following table.
10-5-23 Network Instructions
Note When a double-length operand is used, add 1 to the value shown in the length
column in the following table.
10-5-24 File Memory Instructions
Instruction Mnemonic Code Length
(steps)
(See
note.)
ON execution time (µs) Conditions
CPU6@H-R CPU6@HCPU4@HCPU4@ CJ1M
excluding
CPU11/21
CJ1M
CPU11/21
PROTOCOL
MACRO
PMCR 260 5 100.1 100.1 142.1 276.8 158.4 206.0 Sending 0 words,
receiving 0 words
134.2 134.2 189.6 305.9 210.0 256.7 Sending 249 words,
receiving 249
words
TRANSMIT TXD 236 4 68.5 68.5 98.8 98.8 109.3 102.9 Sending 1 byte
734.3 734.3 1.10 ms 1.10 ms 1.23 ms 1.16 ms Sending 256 bytes
RECEIVE RXD 235 4 89.6 89.6 131.1 131.1 144.0 132.1 Storing 1 byte
724.2 724.2 1.11 ms 1.11 ms 1.31 ms 1.22 ms Storing 256 bytes
TRANSMIT VIA
SERIAL COMMU-
NICATIONS UNIT
TXDU 256 4 131.5 131.5 202.4 --- 213.4 208.6 Sending 1 byte
RECEIVE VIA
SERIAL COMMU-
NICATIONS UNIT
RXDU 255 4 131 131 200.8 --- 211.8 206.8 Storing 1 byte
CHANGE SERIAL
PORT SETUP
STUP 237 3 341.2 341.2 400.0 440.4 504.7 524.7 ---
Instruction Mnemonic Code Length
(steps)
(See
note.)
ON execution time (
µs) Conditions
CPU6@H-R CPU6@HCPU4@HCPU4@ CJ1M
excluding
CPU11/21
CJ1M
CPU11/21
NETWORK SEND SEND 090 4 84.4 84.4 123.9 123.9 141.6 195.0 ---
NETWORK
RECEIVE
RECV 098 4 85.4 85.4 124.7 124.7 142.3 196.7 ---
DELIVER COM-
MAND
CMND 490 4 106.8 106.8 136.8 136.8 167.7 226.7 ---
EXPLICIT MES-
SAGE SEND
EXPLT 720 4 127.6 127.6 190.0 --- 217.0 238.0 ---
EXPLICIT GET
ATT RIBU TE
EGATR 721 4 123.9 123.9 185.0 --- 210.0 232.7 ---
EXPLICIT SET
ATT RIBU TE
ESATR 722 3 110.0 110.0 164.4 --- 188.3 210.3 ---
EXPLICIT WORD
READ
ECHRD 723 4 106.8 106.8 158.9 --- 176.3 220.3 ---
EXPLICIT WORD
WRITE
ECHWR 724 4 106.0 106.0 158.3 --- 175.7 205.3 ---
Instruction Mnemonic Code Length
(steps)
(See
note 1.)
ON execution time (
µs) Conditions
CPU6@H-R CPU6@HCPU4@HCPU4@ CJ1M
excluding
CPU11/21
CJ1M
CPU11/21
READ DATA FILE FREAD 700 5 391.4 391.4 632.4 684.1 657.3 641.3 2-character direc-
tory + file name in
binary
836.1 836.1 1.33 ms 1.35 ms 1.45 ms 1.16 ms 73-character direc-
tory + file name in
binary

Table of Contents